1. Power Supply
The GRNbms MK3 supports both High Voltage (HV) and Low Voltage (LV) operation.
➤ Low Voltage Mode (12 V System)
- Connect 12 V to the „Jump Start“ connector
- This powers the BMS directly for low-voltage applications or setup/configuration
➤ High Voltage Mode
- For high-voltage setups, connect the BMS using the dedicated HV connectors
HV POS Connector:
B+→ Connect directly to Battery PositiveO+→ Output (post-relay) – not required for power supply
HV NEG Connector:
B-→ Connect directly to Battery NegativeO-→ Output (post-relay) – not required for power supply
✅ To power the BMS: only B+ and B- are needed
⚠️ Valid voltage range: 150 V – 1200 V DC Operating the BMS outside this range may cause malfunction or damage.
Additionally, for safety and EMI compliance:
- Connect the battery chassis to the
Epin on the CHASSIS connector - Use a dual connection if possible for redundancy
👉 Details about relay and output wiring can be found here