⚠️ Disclaimer – Safety First!
The wiring diagrams and connection examples provided here are suggestions only and may not cover all edge cases or safety requirements.
All high-voltage components must be installed and verified by a qualified electrician or professional installer.
Incorrect wiring or misuse can lead to severe damage, fire, or personal injury.
The manufacturer assumes no liability for damages resulting from improper installation or handling.
Below is the recommended HV wiring setup for systems using 3 relays and precharge functionality:
E pin): Must be connected to battery chassis – ideally with 2 separate wires
⚠️ Important: The precharge path must always lead through the shunt to ensure current measurement during precharge. The positive and negative relays must remain open during precharge phase and close only after precharge completes.
👉 This wiring ensures proper current monitoring and safe soft-start of the system.
The GRNbms MK3 directly controls all three HV relays using integrated 12 V outputs.
Each relay is connected via its dedicated connector:
👉 We recommend using relays with economizer to avoid unnecessary load on the BMS power supply
✅ Just plug in your relays – the BMS handles power and timing automatically