===== Battery Switch ===== The **Battery Switch** is accessible via the **Sidebar → Battery Switch**.\\ It allows controlled activation and deactivation of the entire battery system. {{:mk3:screenshot2025-04-07202133.png?nolink&300|Battery Switch UI}} ==== System Start-Up ==== After booting, the BMS requires about **120 seconds** for full initialization.\\ Only after this delay the **green "Power On"** button becomes available. ''⏳ During this time, the system runs internal checks and communication initialization.'' ==== Activation Flow ==== === High Voltage Systems === * When **"Power On"** is pressed, the BMS automatically performs an **isolation test** * If the test passes, the **precharge sequence** starts, followed by activation of the positive and negative relays * The system is now live and ready for operation === Low Voltage Systems === * Same flow as above, **but without isolation test** * Relays are closed after a short delay and the inverter is powered up ---- ==== When System is Active ==== {{:mk3:screenshot2025-04-07202141.png?nolink&300}} Once relays are engaged, two buttons become visible: * 🔴 **Emergency Stop** Instantly disables all relays – use only in emergency situations ''⚠️ Cuts power without any shutdown process. May lead to system faults if used during operation.'' * 🔵 **Shutdown** Recommended method for turning the system off ''Sends a clean shutdown signal to the inverter and safely disconnects all relays afterward'' ---- ==== Status Indicators ==== * **State:** Shows current switch/test state (e.g. ''Waiting'', ''Testing Isolation'', ''Ready'', ''Error'') * **Relays:** Displays relay status (e.g. ''Open'', ''Closed'', ''Precharge'', ''Error'') ''🔍 Always check both values before powering on or off the system manually.''